An innovative method for feeding flooded evaporators, arranged in parallel in R744 plants, is presented. In order to promote evaporators overfeeding, an ejector circulates liquid from the low pressure receiver back to the intermediate pressure receiver. Since there is not a need for superheat at the evaporator exit, each evaporator expansion valve can be controlled by a signal representative, either of the evaporator load, or the evaporator performance, such as the air temperature at its inlet or outlet. When compared to dry-expansion evaporator systems, the proposed solution offers energy saving and smooth operating conditions, typical of flooded evaporators, while still maintaining a simple plant lay-out. The concept was experimentally validated: the evaporators were maintained in flooded conditions, while the ejector was able to promote liquid recirculation. Direct comparison with dry-expansion operations was performed. The suggested method is mainly intended for commercial refrigeration plants, where many evaporators are arranged in parallel.

Experimental analysis of a new method for overfeeding multiple evaporators in refrigeration systems

Silvia Minetto;Sergio Marinetti
2014

Abstract

An innovative method for feeding flooded evaporators, arranged in parallel in R744 plants, is presented. In order to promote evaporators overfeeding, an ejector circulates liquid from the low pressure receiver back to the intermediate pressure receiver. Since there is not a need for superheat at the evaporator exit, each evaporator expansion valve can be controlled by a signal representative, either of the evaporator load, or the evaporator performance, such as the air temperature at its inlet or outlet. When compared to dry-expansion evaporator systems, the proposed solution offers energy saving and smooth operating conditions, typical of flooded evaporators, while still maintaining a simple plant lay-out. The concept was experimentally validated: the evaporators were maintained in flooded conditions, while the ejector was able to promote liquid recirculation. Direct comparison with dry-expansion operations was performed. The suggested method is mainly intended for commercial refrigeration plants, where many evaporators are arranged in parallel.
2014
Istituto per le Tecnologie della Costruzione - ITC
CO2
Flooded evaporator
Thermostatic valve
Ejector
Transcritical cycle
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.14243/19399
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact