This paper deals with the issue of measurement device placement for load flow analysis in medium-voltage (MV) distribution networks. The study is carried out using an innovative measurement algorithm for load flow analysis developed by the authors. It is based on low-voltage (LV) load power measurements applied on a backward/forward algorithm for the load flow resolution. The final aim is to identify the most suitable number and placement of the LV measurement points in order to limit the uncertainty on the power flow estimation to a target value. The proposed approach is based on the uncertainty evaluation of the estimated power flows; a sensitivity analysis is performed in order to assess the uncertainty contribution of each LV power measurement to the estimated power flow upstream of each MV feeder of the distribution network. The LV measurement device placement is presented and discussed in a real case study, i.e., the distribution network of the Ustica Island.

LV Measurement Device Placement for Load Flow Analysis in MV Smart Grids

Di Cara D;Tine G
2016

Abstract

This paper deals with the issue of measurement device placement for load flow analysis in medium-voltage (MV) distribution networks. The study is carried out using an innovative measurement algorithm for load flow analysis developed by the authors. It is based on low-voltage (LV) load power measurements applied on a backward/forward algorithm for the load flow resolution. The final aim is to identify the most suitable number and placement of the LV measurement points in order to limit the uncertainty on the power flow estimation to a target value. The proposed approach is based on the uncertainty evaluation of the estimated power flows; a sensitivity analysis is performed in order to assess the uncertainty contribution of each LV power measurement to the estimated power flow upstream of each MV feeder of the distribution network. The LV measurement device placement is presented and discussed in a real case study, i.e., the distribution network of the Ustica Island.
2016
Istituto di iNgegneria del Mare - INM (ex INSEAN)
Advanced metering infrastructure
load flow (LF) analysis
meter placement
power measurements
power quality analyzer (PQA)
power system measurements
power system monitoring
smart grids
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.14243/316799
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 49
  • ???jsp.display-item.citation.isi??? 45
social impact