This work is focused on the measurement uncertainty impact on load flow analysis in medium voltage (MV) distribution networks. In more detail, the paper presents the uncertainty evaluation of a simplified load flow algorithm, which is based on the load power measurements at each secondary substation and one voltage measurement at the slack bus (i.e. the voltage at the MV bus bars of the primary substation). To reduce the costs of the monitoring system, the load flow algorithm makes use of LV load power measurements for all the substations except those of MV users, where MV transducers are usually already installed. The uncertainties on the algorithm input quantities (load powers and slack bus voltage) are calculated, considering the actual values of the loads power factors and currents and the accuracy specifications of the measurement instruments installed in the distribution network. Starting from the input quantities uncertainties, the power flows uncertainties are obtained applying the Monte Carlo analysis. The analysis is carried out on a real test system, i.e. the distribution network of Favignana Island. The compatibility is also shown between the algorithm power flow estimations and the power measurements.

Measurement uncertainty impact on simplified load flow analysis in MV smart grids

Di Cara D;Panzavecchia N;
2018

Abstract

This work is focused on the measurement uncertainty impact on load flow analysis in medium voltage (MV) distribution networks. In more detail, the paper presents the uncertainty evaluation of a simplified load flow algorithm, which is based on the load power measurements at each secondary substation and one voltage measurement at the slack bus (i.e. the voltage at the MV bus bars of the primary substation). To reduce the costs of the monitoring system, the load flow algorithm makes use of LV load power measurements for all the substations except those of MV users, where MV transducers are usually already installed. The uncertainties on the algorithm input quantities (load powers and slack bus voltage) are calculated, considering the actual values of the loads power factors and currents and the accuracy specifications of the measurement instruments installed in the distribution network. Starting from the input quantities uncertainties, the power flows uncertainties are obtained applying the Monte Carlo analysis. The analysis is carried out on a real test system, i.e. the distribution network of Favignana Island. The compatibility is also shown between the algorithm power flow estimations and the power measurements.
2018
Istituto di iNgegneria del Mare - INM (ex INSEAN)
9781538622223
Advanced metering infrastructure (AMI)
Electric load flow
Electric power distribution
Electric power system measurement
Electric power transmission networks
Monitoring
Power quality analyzer
Smart grid
Uncertainty evaluation
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.14243/351707
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 8
  • ???jsp.display-item.citation.isi??? ND
social impact