The contribute describes and analyses some recent experimental results obtained at the High Voltage Padova Test Facility (HVPTF) The results of four voltage hold -off experiments adopting stainless steel electrodes are presented and discussed. The conditioning histories in high vacuum, obtained by a fully automatic procedure, have been compared and analysed. A marked total voltage effect has been observed for gap lengths longer than 70 mm. The best hold -off performances in medium vacuum, up to 800kV, the limit of the system, were obtained by the stationary injection of Ar.

HVDC insulation between shaped electrodes separated by large vacuum gaps

Deambrosis SM;Cervaro V;De Lorenzi A;Fincato M;Martines E;Pasqualotto R;Rossetto F;Zuin M
2019

Abstract

The contribute describes and analyses some recent experimental results obtained at the High Voltage Padova Test Facility (HVPTF) The results of four voltage hold -off experiments adopting stainless steel electrodes are presented and discussed. The conditioning histories in high vacuum, obtained by a fully automatic procedure, have been compared and analysed. A marked total voltage effect has been observed for gap lengths longer than 70 mm. The best hold -off performances in medium vacuum, up to 800kV, the limit of the system, were obtained by the stationary injection of Ar.
2019
Istituto di Chimica della Materia Condensata e di Tecnologie per l'Energia - ICMATE
Istituto per la Scienza e Tecnologia dei Plasmi - ISTP
High Voltage Padova Test Facility
HVPTF
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.14243/392390
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact