This paper describes the development and validation of an innovative protection system based on medium-voltage fuses for a high-power switching conversion system. This special conversion system, rated to deliver about 56 MW to the load, is based on neutral-point clamped IGCT inverters, connected to the same dc link through a set of distributed busbars, with a dc-link voltage of 6.5 kV and a capacitive stored energy up to 837 kJ. The sudden release of this energy in case of a switch failure in one inverter and the subsequent short circuit of one leg can lead to destructive consequences. From the analysis of different protection strategies, performed by numerical simulations of the fault evolutions, the developed solution based on medium-voltage fuses was found the only provision able to cope with such high stored energy and uncommon circuit topology. Custom fuses were developed for this application, and a specially tailored test was designed for validating the fuse selection. The paper, after summarizing the work carried out to simulate the fault evolution and select the protection, presents the analyses carried out to set up the validation test, and describes and discusses the results of the test and the complementing numerical simulations, which demonstrated the effectiveness of the protection system.

Development and Validation of a Special Protection System for Internal Fault in a High-Power Three-Level NPC VSC

Gaio E;
2021

Abstract

This paper describes the development and validation of an innovative protection system based on medium-voltage fuses for a high-power switching conversion system. This special conversion system, rated to deliver about 56 MW to the load, is based on neutral-point clamped IGCT inverters, connected to the same dc link through a set of distributed busbars, with a dc-link voltage of 6.5 kV and a capacitive stored energy up to 837 kJ. The sudden release of this energy in case of a switch failure in one inverter and the subsequent short circuit of one leg can lead to destructive consequences. From the analysis of different protection strategies, performed by numerical simulations of the fault evolutions, the developed solution based on medium-voltage fuses was found the only provision able to cope with such high stored energy and uncommon circuit topology. Custom fuses were developed for this application, and a specially tailored test was designed for validating the fuse selection. The paper, after summarizing the work carried out to simulate the fault evolution and select the protection, presents the analyses carried out to set up the validation test, and describes and discusses the results of the test and the complementing numerical simulations, which demonstrated the effectiveness of the protection system.
2021
Istituto per la Scienza e Tecnologia dei Plasmi - ISTP
Inglese
14
18
5937-1
5937-18
18
https://www.mdpi.com/1996-1073/14/18/5937
Sì, ma tipo non specificato
voltage source converters
internal fault
protection system
fuses
NPC inverter
IGCT
This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). The work leading to this publication has been funded partially by Fusion for Energy. This work has been carried out within the framework of the EUROfusion Consortium and has received funding from the Euratom research and training program 2014-2018 and 2019-2020 under grant agreement No 633053.
6
info:eu-repo/semantics/article
262
Dan, M; Zanotto, L; Gaio, E; Panizza, C; Finotti, C; Perna, M
01 Contributo su Rivista::01.01 Articolo in rivista
none
   Implementation of activities described in the Roadmap to Fusion during Horizon 2020 through a Joint programme of the members of the EUROfusion consortium
   EUROfusion
   H2020
   633053
File in questo prodotto:
Non ci sono file associati a questo prodotto.

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.14243/395722
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 1
  • ???jsp.display-item.citation.isi??? 0
social impact