This paper presents a study on the use of power factor indicators for the assessment of harmonic distortion sources in power systems. In detail the analysis is focused on the comparison between the proposed nonactive power factor (Q(1)/N) and the indicators of the IEEE Std. 1459-2010, and on the indicators feasibility in identifying the presence of harmonic distortion sources. As discussed in the paper, the proposed indicator can be evaluated with good accuracy, by means of typical power quantities measurements at the point of common coupling (PCC). Thus its measurement can be feasibly implemented in commercial platforms used for smart metering applications. To verify the proposal validity, some simulations were carried out on a benchmark test system recently proposed in literature, where the impact of capacitor banks for reactive power compensation is taken into account.

A single-point approach based on nonactive power factor for the assessment of harmonic distortion sources in power systems

Di Cara Dario;Guaiana Salvatore;Panzavecchia Nicola;Tine Giovanni
2022

Abstract

This paper presents a study on the use of power factor indicators for the assessment of harmonic distortion sources in power systems. In detail the analysis is focused on the comparison between the proposed nonactive power factor (Q(1)/N) and the indicators of the IEEE Std. 1459-2010, and on the indicators feasibility in identifying the presence of harmonic distortion sources. As discussed in the paper, the proposed indicator can be evaluated with good accuracy, by means of typical power quantities measurements at the point of common coupling (PCC). Thus its measurement can be feasibly implemented in commercial platforms used for smart metering applications. To verify the proposal validity, some simulations were carried out on a benchmark test system recently proposed in literature, where the impact of capacitor banks for reactive power compensation is taken into account.
2022
Istituto di iNgegneria del Mare - INM (ex INSEAN)
Power Quality
IEEE 1459-2010
Power Ratio Quantities
File in questo prodotto:
File Dimensione Formato  
prod_476787-doc_194980.pdf

solo utenti autorizzati

Descrizione: A single-point approach based on nonactive power factor for the assessment of harmonic distortion sources in power systems
Tipologia: Versione Editoriale (PDF)
Dimensione 2.28 MB
Formato Adobe PDF
2.28 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.14243/446939
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 1
  • ???jsp.display-item.citation.isi??? 0
social impact