Being the interface between indoor and outdoor, building envelope significantly influences indoor heating and cooling loads and thus affects building energy consumption. This paper presents the results of numerical simulation for the performance prediction of building-integrated photovoltaic/thermal double-skin facade (BIPV/T-DSF). Different BIPV materials (amorphous silicon PV, dye-sensitized solar cell and Perovskite based solar cells) were considered as the exterior cladding of a North-facing facade of an office building located in Australia. The performance assessment involved the selection of three climates in Australia, represented by the cities of Darwin, Sydney and Canberra. The air cavity created between the outer skin and the inner one were alternatively assessed in the non-ventilated, naturally-ventilated and mechanically-ventilated modes of operation, while a full sensitivity analysis was performed in order to assess the influence of different design parameters, such as internal skin's thermal transmittance, cavity depth, ventilation louvres’ opening ratio and cavity ventilation rate. By comparing the different operational modes and BIPV technologies, it was found that naturally-ventilated DSF integrating the Perovskite-based solar cell could be the optimal configuration achieving the highest savings. Total annual energy savings of 34.1%, 86% and 106% annual were reached respectively in Darwin, Sydney and Canberra, in comparison to conventional technologies. In addition, this façade technology could further reduce the building's heating and cooling loads by harvesting thermal energy generated within the air cavity. The study finally demonstrated that the harvested electrical and thermal energy from the façade could cover a significant share of building's energy consumption.

Performance assessment of BIPV/T double-skin façade for various climate zones in Australia: Effects on energy consumption

Cannavale A.
Membro del Collaboration Group
;
Di Carlo A.
Membro del Collaboration Group
;
2020

Abstract

Being the interface between indoor and outdoor, building envelope significantly influences indoor heating and cooling loads and thus affects building energy consumption. This paper presents the results of numerical simulation for the performance prediction of building-integrated photovoltaic/thermal double-skin facade (BIPV/T-DSF). Different BIPV materials (amorphous silicon PV, dye-sensitized solar cell and Perovskite based solar cells) were considered as the exterior cladding of a North-facing facade of an office building located in Australia. The performance assessment involved the selection of three climates in Australia, represented by the cities of Darwin, Sydney and Canberra. The air cavity created between the outer skin and the inner one were alternatively assessed in the non-ventilated, naturally-ventilated and mechanically-ventilated modes of operation, while a full sensitivity analysis was performed in order to assess the influence of different design parameters, such as internal skin's thermal transmittance, cavity depth, ventilation louvres’ opening ratio and cavity ventilation rate. By comparing the different operational modes and BIPV technologies, it was found that naturally-ventilated DSF integrating the Perovskite-based solar cell could be the optimal configuration achieving the highest savings. Total annual energy savings of 34.1%, 86% and 106% annual were reached respectively in Darwin, Sydney and Canberra, in comparison to conventional technologies. In addition, this façade technology could further reduce the building's heating and cooling loads by harvesting thermal energy generated within the air cavity. The study finally demonstrated that the harvested electrical and thermal energy from the façade could cover a significant share of building's energy consumption.
2020
Istituto di Struttura della Materia - ISM - Sede Roma Tor Vergata
Building-integrated photovoltaic/thermal system
Double-skin façade
Energy consumption
Semi-transparent PV glazing
TRNSYS simulation
File in questo prodotto:
File Dimensione Formato  
APEN-S-19-08236 submitted.pdf

accesso aperto

Descrizione: Submitted Copy
Tipologia: Documento in Pre-print
Licenza: Altro tipo di licenza
Dimensione 1.67 MB
Formato Adobe PDF
1.67 MB Adobe PDF Visualizza/Apri
1-s2.0-S0038092X2030150X-main.pdf

solo utenti autorizzati

Descrizione: Articolo pubblicato
Tipologia: Versione Editoriale (PDF)
Licenza: NON PUBBLICO - Accesso privato/ristretto
Dimensione 5.39 MB
Formato Adobe PDF
5.39 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.14243/522323
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 98
  • ???jsp.display-item.citation.isi??? 86
social impact