In the present paper design, realization and testing of a novel small scale adsorption refrigerator prototype based on activated carbon/ethanol working pair is described. Firstly, experimental activity has been carried out for identification of the best performing activated carbon available on the market, through the evaluation of the achievable thermodynamic performance both under air conditioning and refrigeration conditions. Once identified the best performing activated carbon, the design of the adsorber was developed by experimental dynamic performance analysis, carried out by means of the Gravimetric-Large Temperature Jump (G-LTJ) apparatus available at CNR ITAE lab. Finally, the whole 0.5 kW refrigerator prototype was designed and built. First experimental results both under reference air conditioning and refrigeration cycles have been reported, to check the achievable performance. High Specific Cooling Powers (SCPs), 95 W/kg and 50 W/kg, for air conditioning and refrigeration respectively, were obtained, while the COP ranged between 0.09 and 0.11, thus showing an improvement of the current state of the art.

Design, realization and testing of an adsorption refrigerator based on activated carbon/ethanol working pair

Frazzica A.
Primo
;
Palomba V.;Brancato V.;Sapienza A.;Vasta S.;Freni A.;Costa F.;Restuccia G.
2016

Abstract

In the present paper design, realization and testing of a novel small scale adsorption refrigerator prototype based on activated carbon/ethanol working pair is described. Firstly, experimental activity has been carried out for identification of the best performing activated carbon available on the market, through the evaluation of the achievable thermodynamic performance both under air conditioning and refrigeration conditions. Once identified the best performing activated carbon, the design of the adsorber was developed by experimental dynamic performance analysis, carried out by means of the Gravimetric-Large Temperature Jump (G-LTJ) apparatus available at CNR ITAE lab. Finally, the whole 0.5 kW refrigerator prototype was designed and built. First experimental results both under reference air conditioning and refrigeration cycles have been reported, to check the achievable performance. High Specific Cooling Powers (SCPs), 95 W/kg and 50 W/kg, for air conditioning and refrigeration respectively, were obtained, while the COP ranged between 0.09 and 0.11, thus showing an improvement of the current state of the art.
2016
Istituto di Tecnologie Avanzate per l'Energia - ITAE
Activated carbon
Adsorption
Ethanol
Refrigeration
File in questo prodotto:
File Dimensione Formato  
Applied Energy 174.pdf

solo utenti autorizzati

Descrizione: Articolo
Tipologia: Versione Editoriale (PDF)
Licenza: Nessuna licenza dichiarata (non attribuibile a prodotti successivi al 2023)
Dimensione 2.26 MB
Formato Adobe PDF
2.26 MB Adobe PDF   Visualizza/Apri   Richiedi una copia

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.14243/530093
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 63
  • ???jsp.display-item.citation.isi??? 58
social impact