In online single-sided partial discharge (PD) location settings, PD reflection patterns are affected by all components present in the cable circuit. This paper describes the performance of electromagnetic time reversal (EMTR) when interfering reflections contribute to the transient waveforms emitted by the PD. The analysed situation refers to a ring main unit (RMU) in the medium voltage (MV) grid where PD recordings are disturbed by signals reflected from the other cables connected to the RMU, potentially affecting the PD location accuracy. We show that the accuracy of EMTR based location methods is unaffected by such effects.
Electromagnetic time reversal applied to online partial discharge location in power cables: influence of interfering reflections from the cable circuit
A. Ragusa
Primo
;A. Duffy;
2023
Abstract
In online single-sided partial discharge (PD) location settings, PD reflection patterns are affected by all components present in the cable circuit. This paper describes the performance of electromagnetic time reversal (EMTR) when interfering reflections contribute to the transient waveforms emitted by the PD. The analysed situation refers to a ring main unit (RMU) in the medium voltage (MV) grid where PD recordings are disturbed by signals reflected from the other cables connected to the RMU, potentially affecting the PD location accuracy. We show that the accuracy of EMTR based location methods is unaffected by such effects.I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.