Data centre racks produce significant amounts of waste heat, which can be exploited to drive thermally driven cooling technologies such as adsorption chillers. However, integrating adsorption cooling systems close to the IT equipment requires compact machine configurations that facilitate their installation within data-centre cooling infrastructure. This work experimentally and theoretically characterizes a novel compact adsorption chiller prototype designed as a proof-of-concept for rack-integrated adsorption chillers. The prototype introduces a new configuration in which the conventional evaporator and condenser are replaced by direct evaporation/condensation chambers coupled to the adsorber modules. All refrigerant distribution throughout the machine is done in liquid phase, eliminating the need for large vacuum valves for vapor transport, allowing a simpler vacuum-system design. Experimental characterization was performed with hot-water temperatures between 55 and 85 °C and cooling-water temperatures between 25 and 30 °C, while the refrigerant pump flow rate was also varied. The prototype achieved an overall cooling capacity of 5–12 kW, combining high- and low-temperature thermal contributions for the target rack-integrated cooling application, with a maximum thermal COPth of 0.44. As a second contribution, a dynamic model of the new machine configuration was developed, combining a lumped-parameter approach with discretization of the adsorber modules and direct evaporation/condensation chambers. Energy and mass balances describe the thermal and mass-transfer processes within the core components. The combined experimental and theoretical characterization demonstrates the feasibility of the direct evaporation/condensation concept and provides a basis for further development of a compact rack-integrated adsorption chiller driven by low-temperature waste heat from data-centre racks.

Experimental characterization and modelling of a compact adsorption chiller prototype for data Centre cooling

Angelo, Freni
2026

Abstract

Data centre racks produce significant amounts of waste heat, which can be exploited to drive thermally driven cooling technologies such as adsorption chillers. However, integrating adsorption cooling systems close to the IT equipment requires compact machine configurations that facilitate their installation within data-centre cooling infrastructure. This work experimentally and theoretically characterizes a novel compact adsorption chiller prototype designed as a proof-of-concept for rack-integrated adsorption chillers. The prototype introduces a new configuration in which the conventional evaporator and condenser are replaced by direct evaporation/condensation chambers coupled to the adsorber modules. All refrigerant distribution throughout the machine is done in liquid phase, eliminating the need for large vacuum valves for vapor transport, allowing a simpler vacuum-system design. Experimental characterization was performed with hot-water temperatures between 55 and 85 °C and cooling-water temperatures between 25 and 30 °C, while the refrigerant pump flow rate was also varied. The prototype achieved an overall cooling capacity of 5–12 kW, combining high- and low-temperature thermal contributions for the target rack-integrated cooling application, with a maximum thermal COPth of 0.44. As a second contribution, a dynamic model of the new machine configuration was developed, combining a lumped-parameter approach with discretization of the adsorber modules and direct evaporation/condensation chambers. Energy and mass balances describe the thermal and mass-transfer processes within the core components. The combined experimental and theoretical characterization demonstrates the feasibility of the direct evaporation/condensation concept and provides a basis for further development of a compact rack-integrated adsorption chiller driven by low-temperature waste heat from data-centre racks.
2026
Istituto di Chimica dei Composti Organo Metallici - ICCOM - Sede Secondaria Pisa
Adsorption chiller
Data Centre cooling
Direct evaporation/condensation
Lumped-parameter model
Rack-integrated cooling
File in questo prodotto:
File Dimensione Formato  
Applied Thermal Engineering 309 (2026) 133754.pdf

accesso aperto

Descrizione: VoR
Tipologia: Versione Editoriale (PDF)
Licenza: Creative commons
Dimensione 5.95 MB
Formato Adobe PDF
5.95 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/20.500.14243/607662
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 0
  • ???jsp.display-item.citation.isi??? ND
social impact